CAN bus troubleshooting

Work through these in order. The first two account for most cases.

  1. Is it powered? The SYS LED lights as soon as the board has input voltage. Off means power, not CAN. USB-C does not power the board — main input is required.
  2. Measure termination. With the robot off, measure resistance across CANH and CANL. About 60 Ω is correct: two 120 Ω terminators in parallel. Reading 120 Ω means only one terminator is present. Reading much higher means neither is.
  3. Check the jumpers. Close both termination jumpers only when the module is physically at an end of the bus. Opening either one disables the whole termination network — they form a single split network, not two independent ones.
  4. Green and yellow. CAN wiring is conventionally yellow for CANH and green for CANL. Swapped pairs are the classic mistake and produce a bus that looks wired and does not work.
  5. Tug every crimp. A crimp that looks fine and fails under vibration is the most common intermittent fault in FRC, and it presents as a device that disappears mid-match.

DEVICE_ID_CONFLICT means another device answers on the same device type and number. ROTEM detects this continuously and reports it — it will not silently renumber itself, because a device that quietly changes address is far harder to debug than one that complains.

Device numbers are scoped per device type, so an AHRS and an encoder can both be device 0 without conflicting. Assign a new number over USB with no bus and no deployed robot code.

Read the diagnostics before changing anything:

imu.getYawUncertainty(); // the filter's own confidence
imu.getAccumulatedDrift(); // estimated error since the last zero
imu.getActiveAlerts(); // what the device thinks is wrong
  • High vibration — mechanical, not electrical. Check module bearings and belt tension.
  • Magnetic disturbance — a current-carrying conductor or a steel mechanism near the board. Corrections are suspended automatically; heading is not stepped.
  • Sensor saturation — motion exceeded the configured range during an impact. Accuracy is degraded for that interval and recovers.
  • Estimator fault — the filter hit a numerical fault and reinitialised rather than publish a plausible-looking wrong orientation. Heading is untrustworthy until it reports converged.

BUS_OFF almost always means a wiring fault or a bit-rate mismatch rather than a device fault. Recovery is automatic and the counter is published in the CAN health frame. If it repeats, inspect the wiring before replacing hardware.